Electrical control boxes and panels
Variable frequency drive panels
The pump speed adapts to demand: constant pressure, energy savings, smooth starts. Standard drive panels up to 22 kW, or dedicated pumping drive panels up to 160 kW with PID control, pipe-fill control and pressure-loss detection. 4-20 mA input for external control.
- Energy savingsThe pump runs at just the speed needed; energy-saving mode on pumping drives.
- PID controlConstant pressure or flow, pipe-fill control and pressure-loss detection.
- 4-20 mA controlSpeed set by an external 4-20 mA signal: PLC, controller or SCADA.
- Up to 3 pumpsAutomatic duty rotation, speed control on all motors (standard drive).
Specifications
| Standard drive | Single-phase 230 V (three-phase output) 0.75 to 2.2 kW; three-phase 400 V 0.75 to 22 kW; 1 to 3 motors |
|---|---|
| Pumping drive | Three-phase 400 V, 2.2 to 160 kW; 1 to 3 motors (speed control on motor no. 1) |
| Functions | Display, simple programming, alarm and event log, remote monitoring |
| Pumping functions | PID, level and pipe-fill control, pressure-loss detection, energy-saving mode |
| Equipment | Lockable isolator, AUTO / MANU keys, drive and auxiliary fuses, forced ventilation with filters |
| Inputs | 4-20 mA; 2 inputs for probes or float switches |
| Enclosure | Metal IP54, from -5 to +40 °C |
The panels
Part numbers in the catalogue
Standard drive panel0.75 to 22 kW, 1 to 3 motors
Pumping drive panel2.2 to 160 kW, PID control