PIC proportional injection controller

Automation and control

New

PIC proportional injection controller

The PIC (Proportional Injection Controller) is the injection controller designed by Aqua'Tec. It measures the water flow and continuously adjusts the injection of one or two dosing pumps, taking into account the commands and safety interlocks on site. Variable flow, accurate dosing.

Designed and developed in France
  • Proportional to the actual flowThe PIC reads the water meter and adjusts the injection in real time: the concentration stays constant when the flow changes.
  • 1 or 2 independent pumpsEach channel has its own set point (in % or ppm): two chemicals dosed in parallel, each at the right concentration.
  • 4-20 mA controlTwo independent analogue outputs directly drive ElectroFlow pumps and MecaFlow pumps with integrated drive.
  • Multi-zone fertigationThe irrigation controller selects the set points and enables each pump zone by zone; the PIC keeps the proportion.
  • Site safetyLow levels, pH and conductivity alarms, external stops: dosing is enabled or cut according to your conditions.
  • 12 inputs, 12 outputsMeter, 9 configurable inputs and 2 × 4-20 mA inputs; 2 × 4-20 mA outputs, 4 pulse outputs and 6 relays.

Specifications

FunctionMulti-pump proportional injection controller
Pumps controlled1 or 2, with independent set points
Meter input1, pulse water meter (reed contact)
Digital inputs9 configurable: dry contact or 24 Vac / 24 Vdc, NO / NC logic
Analogue inputs2 × 4-20 mA
Analogue outputs2 × independent 4-20 mA (pump control)
Pulse outputs4, isolated
Relay outputs6 (status feedback, alarms)
InterfaceGraphic display and function keys: dosing, configuration, diagnostics, information
ApplicationsIrrigation, fertigation, water treatment, disinfection, chemical injection, industrial processes

Documents

How it works

Measure the flow. Adjust the injection. Keep the proportion. The PIC receives the pulses from the water meter, calculates the network flow and controls each dosing pump to meet the set point, whatever the flow at the time. Field inputs (contacts, levels, alarms) enable or cut dosing.

General architecture of the PIC: meter input, configurable inputs, pulse, relay and 4-20 mA outputs

Typical configurations

One pump: the injection follows the flow

A MecaFlow dosing pump controlled in 4-20 mA through a variable frequency drive: when the water flow increases, the injection increases in the same proportion.

Proportional dosing with a MecaFlow dosing pump

Two pumps, two independent chemicals

An ElectroFlow pump for a low flow (for example an acid at 64 ppm) and a MecaFlow for a high flow (a fertiliser at 1%): each chemical keeps its own set point.

Proportional dosing with two independent pumps

pH and conductivity safety

Combined with a 46D analyser-controller, the PIC receives the pH and conductivity alarms and cuts the relevant injection if readings drift.

pH and conductivity safety with an analyser

Multi-zone fertigation

For each zone, the set points and the enabled pumps can change. The irrigation controller stays in charge of the sequence: its contacts select the set point and enable P1 / P2, and the PIC automatically keeps the proportion when the network flow changes.

Example of a sequence driven by the irrigation programme

One or two pumps enabled depending on the zone

A controller designed to communicate with the installation

The PIC does more than drive a pump: it integrates with the site’s signals. Water meter, dry contacts, enables, levels, set point selection and external alarms as inputs; 4-20 mA commands, pulse outputs, relays and status feedback as outputs.

PIC inputs and outputs

Which equipment does it work with?